TDK EPCOS GDT Gas Discharge Tube Surge Arrester B88069X8300* 3-electrode arrester T83-A90X
Electrical specifications
DC spark-over voltage 1) 2) 3) |
90 |
V |
Tolerance |
±20 |
% |
Min. |
72 |
V |
Max. |
108 |
V |
Impulse spark-over voltage 3) |
|
|
at 100 V/µs - for 99% of measured values |
< 400 |
V |
- typical values of distribution |
< 300 |
V |
at 1 kV/µs - for 99% of measured values |
< 550 |
V |
- typical values of distribution |
< 500 |
V |
Service life |
|
|
10 operations 50 Hz; 1 s 4) |
10 |
A |
1 operation 50 Hz; 0.18 s (9 cycl.) 4) |
40 |
A |
10 operations [5× (+) & 5× (–)] 8/20 µs 4) |
10 |
kA |
1 operation 8/20 µs 4) |
15 |
kA |
1 operation 10/350 µs 4) |
2 |
kA |
300 operations [150× (+) & 150× (–)] 10/1000 µs 4) |
200 |
A |
Insulation resistance at 50 VDC 3) |
> 10 |
GW |
Capacitance at 1 MHz 3) |
< 1.5 |
pF |
Transverse delay time 5) |
< 0.2 |
µs |
Arc voltage at 1 A |
~ 15 |
V A V |
Glow to arc transition current |
< 0.5 |
|
Glow voltage |
~ 70 |
|
Weight |
~ 1.4 |
g |
Operation and storage temperature |
-40 ... +125 |
°C |
Climatic category (IEC 60068-1) |
40/125/21 |
|
Marking, red negative |
90 YY O 90 - Nominal voltage YY - Year of production O - Non radioactive |
|
Certifications |
UL 497B (E163070) |
1) At delivery AQL 0.65 level II, DIN ISO 2859
2) In ionized mode
3) Tip or ring electrode to center electrode
4) Total current through center electrode, half value through tip respectively ring electrode.
5) Test according to ITU-T Rec. K.12
Terms in accordance with ITU-T Rec. K.12 and IEC 61643-311.
Dimension
Dimensional drawing in mm
The Others
-
FEATURES
* Standard size* Fast response time* Very high current rating* Stable performance over life* Very low capacitance* High insulation resistance* RoHS-compatible -
APPLICATIONS
* Telecommunications* Line protection* Base station protection